Indicate in a table how you would specify the inputs and outputs to achieve effective control of the AHU by the BMS. An example of the type of table required is illustrated below.
Controller interface Points |
Field device e.g. sensor type/actuator etc. |
Input value or control action |
Universal Input 1 |
Inlet Low temperature sensor |
Detecting low temp values and activate the actuator |
Universal Input 2 |
High temperature sensor |
Detecting high temp values |
Universal Input 3 |
Hot water Flow sensor |
Excites flow in the hot water line |
Universal Input 4 |
Volume sensor |
Detects volume of air allowed in the chambers |
Universal Input 5 |
Voltage controller |
Controls source voltage hence optimized performance |
Universal Input 6 |
AHU damper inlet actuator |
Regulates the amount of air entering damper |
Universal Input 7 |
Air pressure control at inlet |
Regulates air pressure at the inlet |
Universal Input 8 |
Self adjusting valve actuator |
Automatic closing and opening of valves |
Universal Input 9 |
Chilled water flow sensor |
Excites the flow in the chilled water line |
Universal Input 10 |
Fan actuator |
Allows fan to draw in air when required |
Analogue Output 1 |
Voltage sensor in input 1 |
Regulated current to sensor 1 |
Analogue Output 2 |
Voltage sensor 2 |
Regulated current to sensor 2 |
Analogue Output 3 |
Voltage sensor 3 |
Regulated current to sensor 3 |
Analogue Output 4 |
Voltage sensor 4 |
Regulated current to sensor 4 |
Analogue Output 5 |
Voltage sensor 5 |
Regulated current to sensor 5 |
Analogue Output 6 |
Voltage sensor 6 |
Regulated current to sensor 6 |
Analogue Output 7 |
Voltage sensor 7 |
Regulated current to sensor 7 |
Analogue Output 8 |
Voltage sensor 9 |
Regulated current to sensor 9 |
This AHU is used to implement an optimum start and stop energy saving strategy for the building. Describe how this would be implemented and how the BMS outstation/controller would interact with the AHU, i.e. the sensor data used, the control actions over the course of a working day in the winter months (northern hemisphere) to implement this strategy. It is important to also describe the way in which the BMS outstation/controller might be programmed to allow it to decide when to operate plant.
Optimum performance is often desired such that the system is only used when needed. And this is implemented as follows:
A key field device in this BMS is the temperature sensor. A typical sensor type used in this application is the platinum resistance thermometer (PRT) that can be used in the form of a probe into the AHU or the associated ductwork.
The relationship between temperature sensed and resistance generated for a PRT can be defined by the following equation over a limited range:
Rt= Ro(1+αt)
R0 = Resistance at 0°C (Ω) given as 100 Ω
α = temperature coefficient for platinum (K-1)= 3.9 x10-3
t = temperature sensed (°C)= 109oC
If the PRT is defined as a PT100 (Resistance at 0°C = 100 Ω) and the value of temperature coefficient for platinum is 3.9 x 10-3 per degree K.
If a PRT PT100 sensor is used to measure the air temperature in the return air duct of the air handling unit and it reads 109 Ω at the sensor, what is the air temperature in the duct as measured by the PRT to the nearest degree Celsius?
Solution:
We simply substitute in the given equation:
Rt =100(1+3.9×10-3 x 109)
= 143oC
The dampers used to divert air in the AHU would be operated by an actuator controlled by the BMS outstation/controller. List and describe the elements of the specification that you would consider in selecting a suitable actuator to control the inlet air damper.
-The damper inlet valve must control air inflow appropriately and in real time fashion
MSc Building Services Engineering – Building Management Systems
The central air-handling unit (AHU) is in a plant room. Analogue signals are transmitted using cables between sensors and the BMS outstation/controller located within this plant room. What is the appropriate form of topology for :
Sensorcabling between BMS outstation/controller and the various sensors
-Interoperability
Cablingbetween this outstation/controller and another outstation/controller elsewhere in the building controlling lightin
-Linking optimization and modulation
How does the risk of signal error arise in the transmission of these analogue signals, and what can be done to minimize these errors?
-Error in transmission occurs during modulation, transit and demodulation. There is need to harmonize these three phases in transmission so that frequencies are matched.
-During modulation, the transmitted data becomes more vulnerable to distortion due to external disturbances such as noise (Sherman and Walker, 2009)
A sensor is installed to measure the outside air temperature with an accuracy of ± 0.5 °C. The BMS will convert the analogue signal from this sensor to a digital signal. The temperature measurement is limited to a range of -10 to 50 °C.
What is the minimum number of digits required to represent the temperature value while ensuring that the error band is less than 0.5 °C?
The uncertainty in this case would be: 0.5/(50+10)= 0.00833 approximately 0.008
Hence there will be at least 4 digits (including the whole number part)
The user of the BMS wishes to log the outside air temperature data from the sensor Part 2.3 above. The temperature values are digitally encoded using the number of bits calculated in Part 2.3.
Suggest, with a justification, a suitable sampling interval for the outside air temperature data.
-A suitable interval would be 0.005 given the calculated uncertainty
If the data were stored as digital information in bytes, what is the minimum number of bytes of memory capacity required to store the data for 30 days?
= 30 x 0.005= 0.15GB
If one hour’s data were transmitted using a simple Hamming Code, how many check bits would be used?
0.15×1/(30×24)x1000= 0.2083, hence 4 check bits
To control the capital costs, the BMS (of which the AHU outstation controller forms part) is required to share data cabling with other ICT systems in the building.
Describe the steps you would take in specification of the BMS components to ensure interoperability with the other systems making careful references to existing international standards, protocols, etc. You will need to demonstrate your knowledge of one of the leading protocols in reasonable depth.
-A good example is the supervisor to supervisor protocol in which at the level of management, the distinct management systems interact. The standard used in this case is the BACNet
– Normally it is used to manage communication sessions such that departmental exchanges are facilitated and prompt response to emergency such as fire outbreak is appropriately coordinated. These exchanges of information would normally be in the form of multiple back-and-forth transmissions between two nodes.
What approach would be taken to cabling in the building if was to be constructed on a university campus with an existing BMS and ICT network. You should consider and describe the approach taken with reference to current international standards.
The major functional approach would be interoperability where the systems are designed to complement each other in a manner that optimizes the overall performance.
If the BMS were to be required to provide enthalpy control of the conditioned space what control strategies would be implemented. Include in your response a detailed description of the typical constraints and how the conflicting demands of enthalpy control and air quality control would be managed by the BMS outstation/controller serving the AHU in Fig 1. (Assume that the supply and extract fans are controlled by variable speed drives).
The following are the control strategies to be adopted:
Notably, these two strategies somehow present a conflicting scenario in which efficient space heating required would mean less amount of air is to be allowed by the damper inlet; However, to increase the air quality, more air would be needed to maintain the inside conditions. This then requires some sought of balance between the two strategies and it is achieved as follows:
– The fan speed is made adjustable so that it can admit either less or more air per unit time.
Normally, the set points are established prior to the building enthalpy control, where the exact objectives are formulated. The BMS would calculate the ventilation ratio such that if found to be lower than the set point value, a signal is sent to the fan to increase its speed for more outside air to be allowed. However, at times enthalpy control could be prioritized where energy efficiency overrides the ventilation requirements.
Continuous humidity maintenance is facilitated by the psychometric chart embedded in the system. This chart provides real-time indication on the humidity situation of the inside air and signals are sent to the humidity sensors for appropriate actuation. This works together with the temperature sensor (HVAC, 2018).
Lastly, the BMS would calculate the ventilation ratio which is the ratio between the outside to inside air in a bid to optimize the quality of air within the space and ensure it is consistent with the humidity and temperature conditions.
References
Electronic design. (2018). Understanding Modern Digital Modulation Techniques. [online] Electronic Design. Available at: https://www.electronicdesign.com/communications/understanding-modern-digital-modulation-techniques [Accessed 13 Mar. 2018].
Goleniewski, L. (2018). Analog and Digital Transmission | Telecommunications Technology Fundamentals | InformIT. [online] Informit.com. Available at: https://www.informit.com/articles/article.aspx?p=24687&seqNum=5 [Accessed 13 Mar. 2018].
HVAC, H. (2018). DDC Control Module for an Air Handling Unit | HVAC Control. [online] High Performance HVAC Heating & Cooling. Available at: https://highperformancehvac.com/ddc-control-module-air-handling-unit/ [Accessed 13 Mar. 2018].
Knx.org. (2018). KNX Association – KNX Association [Official website]. [online] Available at: https://www.knx.org/knx-en/index.php [Accessed 13 Mar. 2018].
Reginald, A. (2015). Integrating BIM with BMS in Energy Performance Assessment. International Journal of 3-D Information Modeling, 4(1), pp.19-44.
Sherman, M. and Walker, I. (2009). Measured Air Distribution Effectiveness for Residential Mechanical Ventilation. HVAC&R Research, 15(2), pp.211-229.
Users.cs.fiu.edu. (2018). Calculating the Hamming Code. [online] Available at: https://users.cs.fiu.edu/~downeyt/cop3402/hamming.html [Accessed 13 Mar. 2018].
YouTube. (2018). AHU(air handling unit) working through BMS system (hvac stream). [online] Available at: https://www.youtube.com/watch?v=DaCmHEjz6p4 [Accessed 13 Mar. 2018].
We provide professional writing services to help you score straight A’s by submitting custom written assignments that mirror your guidelines.
Get result-oriented writing and never worry about grades anymore. We follow the highest quality standards to make sure that you get perfect assignments.
Our writers have experience in dealing with papers of every educational level. You can surely rely on the expertise of our qualified professionals.
Your deadline is our threshold for success and we take it very seriously. We make sure you receive your papers before your predefined time.
Someone from our customer support team is always here to respond to your questions. So, hit us up if you have got any ambiguity or concern.
Sit back and relax while we help you out with writing your papers. We have an ultimate policy for keeping your personal and order-related details a secret.
We assure you that your document will be thoroughly checked for plagiarism and grammatical errors as we use highly authentic and licit sources.
Still reluctant about placing an order? Our 100% Moneyback Guarantee backs you up on rare occasions where you aren’t satisfied with the writing.
You don’t have to wait for an update for hours; you can track the progress of your order any time you want. We share the status after each step.
Although you can leverage our expertise for any writing task, we have a knack for creating flawless papers for the following document types.
Although you can leverage our expertise for any writing task, we have a knack for creating flawless papers for the following document types.
From brainstorming your paper's outline to perfecting its grammar, we perform every step carefully to make your paper worthy of A grade.
Hire your preferred writer anytime. Simply specify if you want your preferred expert to write your paper and we’ll make that happen.
Get an elaborate and authentic grammar check report with your work to have the grammar goodness sealed in your document.
You can purchase this feature if you want our writers to sum up your paper in the form of a concise and well-articulated summary.
You don’t have to worry about plagiarism anymore. Get a plagiarism report to certify the uniqueness of your work.
Join us for the best experience while seeking writing assistance in your college life. A good grade is all you need to boost up your academic excellence and we are all about it.
We create perfect papers according to the guidelines.
We seamlessly edit out errors from your papers.
We thoroughly read your final draft to identify errors.
Work with ultimate peace of mind because we ensure that your academic work is our responsibility and your grades are a top concern for us!
Dedication. Quality. Commitment. Punctuality
Here is what we have achieved so far. These numbers are evidence that we go the extra mile to make your college journey successful.
We have the most intuitive and minimalistic process so that you can easily place an order. Just follow a few steps to unlock success.
We understand your guidelines first before delivering any writing service. You can discuss your writing needs and we will have them evaluated by our dedicated team.
We write your papers in a standardized way. We complete your work in such a way that it turns out to be a perfect description of your guidelines.
We promise you excellent grades and academic excellence that you always longed for. Our writers stay in touch with you via email.